| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured. |
| Affected devices do not properly enforce user authentication on specific API endpoints. This could facilitate an unauthenticated remote attacker to circumvent authentication and impersonate a legitimate user. Successful exploitation requires that the attacker has learned the identity of a legitimate user. |
| A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread.
This could allow an unauthenticated remote attacker to crash the network service. |
| A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to a local privilege escalation due to an exposed debug interface on the localhost. This allows any local user to gain code execution as administrative application user. |
| A vulnerability has been identified in Altair Grid Engine (All versions < V2026.0.0). Affected products do not properly validate environment variables when loading shared libraries, allowing path hijacking through malicious library substitution.
This could allow a local attacker to execute arbitrary code with superuser privileges by manipulating the environment variable and placing a malicious library in the controlled path. |
| A vulnerability has been identified in SIMATIC STEP 7 Safety V16 (All versions < V16 Update 7), SIMATIC STEP 7 Safety V17 (All versions < V17 Update 7), SIMATIC STEP 7 Safety V18 (All versions < V18 Update 2), SIMATIC STEP 7 V16 (All versions < V16 Update 7), SIMATIC STEP 7 V17 (All versions < V17 Update 7), SIMATIC STEP 7 V18 (All versions < V18 Update 2), SIMATIC WinCC Unified V16 (All versions < V16 Update 7), SIMATIC WinCC Unified V17 (All versions < V17 Update 7), SIMATIC WinCC Unified V18 (All versions < V18 Update 2), SIMATIC WinCC V16 (All versions < V16.7), SIMATIC WinCC V17 (All versions < V17.7), SIMATIC WinCC V18 (All versions < V18 Update 2), SIMOCODE ES V16 (All versions < V16 Update 7), SIMOCODE ES V17 (All versions < V17 Update 7), SIMOCODE ES V18 (All versions < V18 Update 2), SIMOTION SCOUT TIA V5.4 SP1 (All versions), SIMOTION SCOUT TIA V5.4 SP3 (All versions), SIMOTION SCOUT TIA V5.5 SP1 (All versions), SINAMICS Startdrive V16 (All versions), SINAMICS Startdrive V17 (All versions), SINAMICS Startdrive V18 (All versions), SIRIUS Safety ES V17 (All versions < V17 Update 7), SIRIUS Safety ES V18 (All versions < V18 Update 2), SIRIUS Soft Starter ES V17 (All versions < V17 Update 7), SIRIUS Soft Starter ES V18 (All versions < V18 Update 2), Soft Starter ES V16 (All versions < V16 Update 7), TIA Portal Cloud V3.0 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing hardware configuration profiles. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected systems use symmetric cryptography with a hard-coded key to protect the communication between client and server. This could allow an unauthenticated remote attacker to compromise confidentiality and integrity of the communication and, subsequently, availability of the system.
A successful exploit requires the attacker to gain knowledge of the hard-coded key and to be able to intercept the communication between client and server on the network. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected application does not properly limit the size of specific logs. This could allow an unauthenticated remote attacker to exhaust system resources by creating a great number of log entries which could potentially lead to a denial of service condition. A successful exploitation requires the attacker to have access to specific SIMATIC RTLS Locating Manager Clients in the deployment. |
| A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition. |
| A vulnerability has been identified in syngo.plaza VB30E (All versions < VB30E_HF05). The affected application do not properly sanitize input data before sending it to the SQL server. This could allow an attacker with access to the application could use this vulnerability to execute malicious SQL commands to compromise the whole database. |
| A vulnerability has been identified in NX (All versions < V2406.3000). The affected applications contains an out of bounds read vulnerability while parsing specially crafted PRT files. This could allow an attacker to crash the application or execute code in the context of the current process. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Report Clients do not properly protect credentials that are used to authenticate to the server. This could allow an authenticated local attacker to extract the credentials and use them to escalate their access rights from the Manager to the Systemadministrator role. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected components do not properly authenticate heartbeat messages. This could allow an unauthenticated remote attacker to affected the availability of secondary RTLS systems configured using a TeeRevProxy service and potentially cause loss of data generated during the time the attack is ongoing. |
| A vulnerability has been identified in Polarion V2404 (All versions < V2404.5), Polarion V2410 (All versions < V2410.2). The affected application allows arbitrary JavaScript code be included in document titles. This could allow an authenticated remote attacker to conduct a stored cross-site scripting attack by creating specially crafted document titles that are later viewed by other users of the application. |
| A vulnerability has been identified in SINUMERIK 828D PPU.4 (All versions < V4.95 SP5), SINUMERIK 828D PPU.5 (All versions < V5.25 SP1), SINUMERIK 840D sl (All versions < V4.95 SP5), SINUMERIK MC (All versions < V1.25 SP1), SINUMERIK MC V1.15 (All versions < V1.15 SP5), SINUMERIK ONE (All versions < V6.25 SP1), SINUMERIK ONE V6.15 (All versions < V6.15 SP5). The affected application improperly validates authentication for its VNC access service, allowing access with insufficient password verification.
This could allow an attacker to gain unauthorized remote access and potentially compromise system confidentiality, integrity, or availability. |
| A vulnerability has been identified in RUGGEDCOM RMC8388 V5.X (All versions < V5.10.1), RUGGEDCOM RS416Pv2 V5.X (All versions < V5.10.1), RUGGEDCOM RS416v2 V5.X (All versions < V5.10.1), RUGGEDCOM RS900 (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RS900G (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RSG2100 (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RSG2100P (32M) V5.X (All versions < V5.10.1), RUGGEDCOM RSG2288 V5.X (All versions < V5.10.1), RUGGEDCOM RSG2300 V5.X (All versions < V5.10.1), RUGGEDCOM RSG2300P V5.X (All versions < V5.10.1), RUGGEDCOM RSG2488 V5.X (All versions < V5.10.1), RUGGEDCOM RSG907R (All versions < V5.10.1), RUGGEDCOM RSG908C (All versions < V5.10.1), RUGGEDCOM RSG909R (All versions < V5.10.1), RUGGEDCOM RSG910C (All versions < V5.10.1), RUGGEDCOM RSG920P V5.X (All versions < V5.10.1), RUGGEDCOM RSL910 (All versions < V5.10.1), RUGGEDCOM RST2228 (All versions < V5.10.1), RUGGEDCOM RST2228P (All versions < V5.10.1), RUGGEDCOM RST916C (All versions < V5.10.1), RUGGEDCOM RST916P (All versions < V5.10.1). Affected devices do not properly validate input during the TLS certificate upload process of the web service. This could allow an authenticated remote attacker to trigger a device crash and reboot, leading to a temporary Denial of Service on the device. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The "DBTest" tool of SIMATIC RTLS Locating Manager does not properly enforce access restriction. This could allow an authenticated local attacker to extract sensitive information from memory. |
| A vulnerability has been identified in SIMATIC STEP 7 Safety V18 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing user-controllable input. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300. |
| A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to extraction of database credentials via a world-readable credential file. This allows an attacker to connect to the database as privileged application user and to run system commands via the database. |
| A vulnerability has been identified in SIMATIC S7-200 SMART CPU CR40 (6ES7288-1CR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU CR60 (6ES7288-1CR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA1) (All versions). Affected devices do not properly handle TCP packets with an incorrect structure. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the network cable of the device needs to be unplugged and re-plugged. |